6.6 Set Points
After configuring the Analog Output a Set Point can be configured for that output. If No is selected
and [ENTER] is pressed then the Quick Setup is done and the menus are exited without setting
any Set Point.
Selecting Yes and pressing [ENTER] means a Set Point can be configured. Following Set Point
Types can be selected:
Off (Set Point is Off)
High (High value has to be set)
Low (Low value has to be set)
Outside (High and Low value has to be set)
Between (High and Low value has to be set)
Total Flow (Available only if units of total flow are chosen. A Total Flow value has to be set)
After setting the Set point value(s) a Relay (none (blank), 1, 2, 3, 4) can be configured for that
Set Point. The Relay delay is set to 10 seconds and the Hysteresis is set to 5%.
Press [ENTER] to bring up the Save Changes dialog.